XLPE Insulated Amoured Power Cable
Application: For Outdoor And Indoor Installation In Damp And Wet Locatios Laid Direct In The Ground, In Duct, In Trenches And In Steel Support Brackets.
TYPE: N2XRY Cu/XLPE/BD(PVC)/SWA/PVC
Standard :IEC 60502
Rated Voltage: 0.6/1 Kv
Conductor: Soft Annealed Copper Wires
Insulation: Cross Linked Polyethylene (XLPE) Compound. Bedding: PVC
Armour: SWA
Sheathing :PVC
Operating Temperatures: 90 C Continuous Normal Operation And 130 C For Emergency Overload Condition And 250°C For Short Circuit Condition.

Number of Cores & cross Section

Nominal Insulation Thickness
Diameter of steel wire
Nominal Sheath Thickness
Approx. Overal diameter
Approx. cable weight
Drun Type
Cable Lenght
mm2
mm
mm
mm
mm
Kg/km
M
2x1.5
0.7
0.9
1.8
13.3
354
90
1000
2x2.5
0.7
0.9
1.8
14.2
400
90
1000
2x4
0.7
0.9
1.8
15.3
464
100
1000
2x 6
0.7
0.9
1.8
16.4
556
100
1000
2x 10
0.7
0.9
1.8
18.2
700
110
1000
2x 16
0.7
0.9
1.8
20.2
900
120
1000
2x 25
0.9
1.60
1.8
25.2
1550
140
1000
2x 35
0.9
1.60
1.8
27.3
1840
150
1000
3 x1.5
0.7
0.9
1.8
14.6
395
90
1000
3x2.5
0.7
0.9
1.8
15.4
450
100
1000
3x4
0.7
0.9
1.8
16.5
590
100
1000
3x6
0.7
0.9
1.8
17.1
640
110
1000
3x10
0.7
0.9
1.8
19.1
820
120
1000
3x16
0.7
0.9
1.8
21.3
1085
120
1000
3x25
0.9
1.60
1.8
27.2
1980
150
1000
3x35
0.9
1.60
1.8
29.8
2420
120
1000
3x50
1.0
1.60
1.9
29.6
2530
160
500
3x70
1.1
1.60
2.0
33.6
3510
180
500
3x 95
1.1
2.00
2.2
37.4
4550
190
500
3x120
1.2
2.00
2.3
40.8
5430
220
500
3 x150
1.4
2.00
2.5
45.7
6860
240
500
The above data is approximate and subject to manufacturing tolerance
Delivery lenght tolerance is ± 5 %
Continue ...