TABLE 7
TREFOIL OR FLAT FORAMTION DERATING FACTORS FOR MULTI-CORE
CABLES LAID DIRECT IN GROUND. |
NUMBER OF CIRCUITS |
|
|
| TREFOIL FORMATION |
FLAT FORMATION |
|
TOUCHING |
SPACING = 0.15 M |
SPACING = 0.30 M |
NR |
TREFOIL |
FLAT |
TREFOIL |
FLAT |
TREFOIL |
FLAT |
2
3
4
5
6 |
081
0.69
0.62
0.58
0.54 |
0.81
0.70
0.63
0.60
0.56 |
0.87
0.76
0.72
0.66
0.63 |
0.87
0.78
0.74
0.70
0.67 |
0.91
0.82
0.77
0.73
0.70 |
0.91
0.84
0.81
0.78
0.76 |
|
TABLE 8
FLAT FORMATION DIRAECTING FOR FACTORS THREE SINGLE CORE
CABLE LAID IN FREE AIR.
|
|
|
|
|
|
|
|
|
|
Clearance = Cable dimeter (d)
Clearance from the wall ≥ 2cm
|
|
Number of troughs |
|
 |
|
1 |
|
2 |
|
3 |
|
|
|
0.92 |
|
0.89 |
|
0.88 |
|
Laid on the Floor |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Number of troughs |
|
|
|
|
|
|
|
 |
Laid cables 1
troughs 2
(circulation of air 3
is res 6 |
|
0.92
0.87
0.84
0.82 |
|
0.89
0.84
0.82
0.80 |
|
0.88
0.83
0.81
0.79 |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
 |
1
Laid 2
on cable racks 3
6 |
|
1.00
0.97
0.96
0.94 |
|
0.97
0.94
0.93
0.91 |
|
0.96
0.93
0.92
0.90
|
|
|
|
|
|
|
|
|
|
|
| Arranged near the wall |
|
0.94 |
|
0.91 |
|
0.89 |
|
 |
|
|
|
|
|
|
|
|
|
| Arranged on the wall |
|
0.89 |
|
0.86 |
|
0.84 |
|
 |
|
|
|
|
|
|
|
|
|
|
|
|