TABLE 9
TREEFOIL TOUCHING FORMATION DERATING FACTORS FOR THREE SINGLE CORE CABLES LAID IN FREE AIR. |
|
|
|
|
|
|
|
|
|
Clearance = 2 (d)
Clearance from the wall ≥ 2cm
|
|
Number of troughs |
|
|
|
1 |
|
2 |
|
3 |
|
|
|
0.95 |
|
0.90 |
|
0.88 |
|
Laid on the Floor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Number of troughs |
|
|
|
|
|
|
|
 |
Laid cables 1
troughs 2
(circulation of air 3
is restricted) 6 |
|
0.95
0.90
0.88
0.86 |
|
0.90
0.85
0.83
0.81 |
|
0.88
0.83
0.81
0.79 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
 |
1
Laid 2
on cable racks 3
6 |
|
1.00
1.00
1.00
1.00 |
|
0.98
0.95
0.94
0.93 |
|
0.96
0.93
0.92
0.90 |
|
|
|
|
|
|
|
|
|
|
Arrangements for which reduction of the current is not necessry |
|
|
|
|
|
|
|
 |
|
|
|
|
|
|
|
|
|
|
TABLE 10
HORIZONTAL OR VERTICAL FORMATION DERATING FACTORS FOR FREE AIR.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Clearance =Cable dimeter (d)
Clearance from the wall ≥ 2cm
|
|
Number of troughs |
|
 |
|
1 |
|
2 |
|
3 |
|
6 |
|
9 |
|
|
|
0.95 |
|
0.90 |
|
0.88 |
|
0.85 |
|
0.84 |
|
Laid on the Floor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Number of troughs |
|
|
|
|
|
|
|
|
|
|
|
 |
Laid cables 1
troughs 2
(circulation of air 3
is restricred) 6 |
|
0.95 0.90 0.88 0.86 |
|
0.90 0.85 0.83 0.81 |
|
0.88 0.83 0.81 0.79 |
|
0.85 0.81 0.79 0.77 |
|
0.84 0.80 0.78 0.76 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
 |
1
Laid 2
on cable racks 3
6 |
|
1.00
1.00
1.00
1.00 |
|
0.98
0.94
0.94
0.93 |
|
0.96
0.93
0.92
0.90 |
|
0.93
0.90
0.89
0.87 |
|
0.92
0.89
0.88
0.86 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Arranged near the wall |
|
1.00 |
|
0.93 |
|
0.90 |
|
0.87 |
|
0.86 |
|
 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Arrangements
for which reduction
of the current
is not necessry |
|
Clearance from the wall ≥ 2 cm |
|
|
|
Clearance
from the
cablesl
≥ 2 d |
|
 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|